- 19 -
69 0045 Input Type Lo Byte Hex value
40-4D Thermocouple JF, C, KF, KC, NF, NC, EF, EC,
TF, TC, SF, SC, RF, RC
50-5C RTD pre-2009: 4-wire DIN°F, 4-wire DIN°C,
4-wire ANSI°F, 4-wire°C, 3-wire DIN°F, 3-wire
DIN°C, 3-wire ANSI°F, 3-wire ANSI°C, 2-wire
DIN°F, 2-wire DIN°C, 2-wire ANSI°F, 2-wire
ANSI°C, Short
50-57 RTD post-2009: DIN°F, DIN°C, ANSI°F,
ANSI°C, Ni°F, Ni°C, Cu°F, Cu°C,
60-64 DC 0.2V, 2V, 20V, 200V, 660V
70-73 DC 2 mA, 20 mA, 200 mA, 5A
A0-A2 Ratio 0.2V, 2V, 20V
80-84 RMS 0.2V, 2V, 20V, 200V, 660V
90-93 RMS 2 mA, 20 mA, 200 mA, 5A
C0-C4 Strain 20, 50, 100, 250, 500 mV
D0-D4 Load Cell 20, 50, 100, 250, 500 mV
E0-E4 Ohms 20, 200, 2000, 20K, 200K
70 0046 Setup
(applicable to
DPM)
M = Meter
F = Function
D = Display
Bits 3:0 Ctrl In 1 Ctrl In 2 Both Reset
Hex 0 M Reset M Hold M Reset
Hex 1 F Reset Pk, Vy M Reset
Hex 2 M Hold Pk, Vy F Reset
Hex 3 M Hold Tare M Reset
Hex 4 Pk, Vy Tare FReset
Hex 5 Tare M Reset M Reset
Hex 6 DP2 DP3 DP5 Neither = DP1
Hex 7 DP3 DP4 DP6 Neither = DP2
Hex 8 F Reset D Blank M Reset
Hex 9 M Hold D Blank M Reset
Hex A Pk, Vy D Blank F Reset
Hex B Tare D Blank M Reset
Hex C Valley Peak F Reset
Hex D Tare T Reset M Reset
Bits 5:4
Hex 00 Scale using Scale, Offset
Hex 01 Scale using Coordinates of 2 Points
Hex 10 Scale using Reading Coordinates
Bit 6 Spare
Bit 7 0 = 60 Hz, 1 = 50 Hz