SELECTED FRONT PANEL SETUP ITEMS FOR SERIAL INPUT METER (not consecutive)
If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.”
Press
Menu
Press Digit
Select Key
Press Value Select
Key
SEtuP
Setup
_000_0
Control inputs 1 and 2
F 1 = Tare, 2 = Tare enable
Control input 2 must be at 0V or grounded for
Tare to operate.
ConFiG
Configu-
ration
__0000 Display mode
Note: Remote modes
S (selection 7) and C
(selection C) are used
for most applications.
6 Remote display (H, K, L commands)
7 Single-value remote display
8 Show 1
st
string value, connected to a counter
9 Show 2
nd
string value, connected to a counter
A Show 3
rd
string value, connected to a counter
B Show 4
th
string value, connected to a counter
C Custom Start, Stop, Skip, Show characters
.ti_Out.
Time-out
_000.00 _000.00 _000.00
_000.00 _000.00
Select digit to flash.
Select 0 thru 9 for flashing digit to set time-out in
seconds. Decimal point location is fixed for 10 ms
resolution.
.SEr 1.
__000UBaud rate
Fixed parameters:
No parity, 8 data bits,
1 stop bit
0 300 baud 1 600 baud
2 1200 baud 3 2400 baud
4 4800 baud 5 9600 baud
6 19200 baud
.SEr 2.
__0000UMeter address Select 0 thru F for addresses 1 thru 15. Select 0. thru
F. (with decimal point) for addresses 16 thru 31.
.SEr 3.
_00000URS485 0 Full duplex 1 Half duplex
___000USerial protocol 0 Custom ASCII 1 Modbus RTU
2 Modbus ASCII
SEr 4.
___000UParity 0 None 1 Odd 2 Even
_Addr
___000 __000 ___000
Modbus address
__158 Select 0 through 9 for flashing digit. Address
range is 1 to 247.