KEYSTROKES FOR SETUP
If the MENU key does not work, see Section 9 “Enabling & Locking Out Menu Items.”
Press
Menu
Press Digit
Select Key
Press Value Select
Key
0000 Setpoint 1: 3 Must be set to Item #3.
0000 Setpoint 2: 3 Must be set to Item #3.
0000 Setpoint 3: 3 Must be set to Item #3.
SourcE
Source to com-
pare to setpoint
0000 Setpoint 4: 3 Must be set to Item #3.
00000
Relay state when alarm is
active
0 Relay 1 on Relay 2 on
1 Relay 1 off Relay 2 on
2 Relay 1 on Relay 2 off
3 Relay 1 off Relay 2 off
00000
Alarm latching or non-
latching (auto reset)
(see Glossary)
0 AL1 auto reset AL2 auto reset
1 AL1 latching AL2 auto reset
2 AL1 auto reset AL2 latching
3 AL1 latching AL2 latching
00000
Alarm operates at and
above setpoint (active
high) or at and below
setpoint (active low).
(see Glossary)
0 AL1 active high AL2 active high
1 AL1 active low AL2 active high
2 AL1 disabled AL2 active high
3 AL1 active high AL2 active low
4 AL1 active low AL2 active low
5 AL1 disabled AL2active low
6 AL1 active high AL2 disabled
7 AL1 active low AL2 disabled
8 AL1 disabled AL2 disabled
00000
Hysteresis mode or band
deviation mode
(see Glossary)
0 AL1 band deviation AL2 band deviation
1 AL1 hysteresis AL2 band deviation
2 AL1 band deviation AL2 hysteresis
3 AL1 hysteresis AL2 hysteresis
4 No deviation or hysteresis on menu.
AL SEt
Alarm Setup
for relays 1 & 2
if detected.
Press until
ALSEt is
displayed.
00000
Number of consecutive
readings in alarm zone to
cause an alarm
0 After 1 reading 4 After 16 readings
1 After 2 readings 5 After 32 readings
2 After 4 readings 6 After 64 readings
3 After 8 readings 7 After 128 readings